Evaluation of the audible noise level on distribution transformers using the Sound Pressure Method

This paper presents the results of audible noise measurements on ten no-load distribution transformers, using the sound pressure method. The tests were conducted in the Audible Noise Laboratory of Universidad del Valle, according to the requirements described in the Colombian Technical Standard NTC...

Full description

Autores:
Tipo de recurso:
Fecha de publicación:
2017
Institución:
Universidad Pedagógica y Tecnológica de Colombia
Repositorio:
RiUPTC: Repositorio Institucional UPTC
Idioma:
eng
OAI Identifier:
oai:repositorio.uptc.edu.co:001/14174
Acceso en línea:
https://revistas.uptc.edu.co/index.php/ingenieria/article/view/6051
https://repositorio.uptc.edu.co/handle/001/14174
Palabra clave:
Audible noise measurement
Background noise
Distribution transformer
Sound pressure level
Sound pressure method
Medición de ruido audible
Método de presión sonora
Nivel de presión sonora
Ruido de fondo
Transformador de distribución
Rights
License
http://purl.org/coar/access_right/c_abf258
Description
Summary:This paper presents the results of audible noise measurements on ten no-load distribution transformers, using the sound pressure method. The tests were conducted in the Audible Noise Laboratory of Universidad del Valle, according to the requirements described in the Colombian Technical Standard NTC 5979. The tests allowed to verify the conformity of the product in respect with the audible noise limits established in the Colombian Technical Standard NTC 5978. In addition, it was possible to identify the effect on noise emissions of two transformers after variating the voltage in the power source. Results show that the noise level emitted by the transformers under test was considerably lower than the limits established in the standard, and was significantly affected by the voltage of the source supply.